This is a focused quick-start for the first power-up of an AXEN R290 monobloc (KS-40W to KS-160W). It covers exactly the connections and settings you touch on day one — wiring, hot water, zones, emitter type and weather compensation — plus a power-up checklist and the common error codes. It is not a replacement for the full installation and service manuals, R290 safety rules, or local electrical regulations. Use it alongside the wiring diagram supplied with the unit.

Installer menu passcode 1212

01Before you start

R290 is propane — a flammable refrigerant. Only certified personnel may install, commission or service the unit.

Switch off all power — unit supply, backup heater and DHW tank supply — before opening the switch box or changing any DIP switch. Never bridge or modify a safety device.

Reaching the installer settings

All settings in this guide live under the Installer Level, which is passcode-protected so end users can't reach it.

  1. From the home page press ⋯ MENU.
  2. Select Installer Level and enter the passcode 1212.
  3. Open System Parameter — every setting below is in here.

Navigate with , confirm with ✓ ENTER, step back with ↶ BACK.

02Cable connections

Most field wiring lands on the terminal block inside the switch box. Follow the wiring diagram on the inside of the switch-box door for the exact unit in front of you.

Power supply

Single-phase units use L · N · PE; three-phase units use R · S · T · N · PE. Use a round crimp terminal with insulation casing, and don't mix wire gauges on one terminal.

Power supply terminal blocks for single-phase (L, N, earth) and three-phase (R, S, T, N) units
Power-supply terminals — single-phase (L, N, PE) and three-phase (R, S, T, N, PE)

Protection: fit a high-speed earth-leakage breaker rated 30 mA (<0.1 s) and a fuse/breaker on the supply line. Use 3-core shielded cable of at least 60245 IEC 57 quality. Take the cable size and breaker/fuse rating from the unit nameplate and the electrical data in the installation manual (size wiring from MCA, fuse from MFA).

Signal & control terminals

Low-voltage controls land on CON1, CN1–CN4 and U19. The most relevant for a typical install:

TerminalPrintConnects to
CON1 ①OFF1 / ON1 / NSV1 3-way valve — DHW diverter
CON1 ②③OFF2/3 · ON2/3 · NSV2 / SV3 3-way valves (e.g. Zone 2 mixing)
CON1 ④P_c / NPumpc — Zone 2 pump
CON1 ⑤P_o / NOutside circulation pump / Zone 1 pump
CON1 ⑦P_d / NDHW recirculation pump
CON1 ⑨AHS1 / AHS2Additional heat source
CON1 ⑬AC_L / AC_L1 / AC_HTRoom thermostat input (high voltage)
CN1CL / COM / HTRoom thermostat input (low voltage)
CN2 / CN3SG / EVUSmart Grid / EVU signals
CN4Cascade communication (module sequence)
U19 ①12V·GND·L_A·L_BWired controller
U19 ②12V·GND·I_A·I_BTo outdoor unit
U19 ③H1 / H2RS485 Modbus (H1-B, H2-A)
Signal and control terminal tables: CON1, CN1 to CN4, and U19
Full signal-terminal reference — CON1, CN1–CN4 and U19

Control-signal types. Type 1 ports are dry contacts (no voltage). Type 2 ports carry 220 V: a load under 0.2 A can connect directly, but a load of 0.2 A or more needs an AC contactor.

03Basic settings

The core commissioning choices. Each opens from Menu › Installer Level › System Parameter.

Activate / deactivate hot water (DHW)

Whether the unit produces hot water at all is set by a DIP switch — SW1-2 — on the main control board inside the unit, not in the controller menu.

SW1-2Result
OFFDHW mode valid — hot water enabled; the DHW tile appears on the home page.
ONDHW mode disabled — space heating / cooling only, no DHW tile.

Switch off all power before changing any DIP switch. DHW also needs the DHW tank sensor (Tw) and the SV1 3-way valve wired (see Cable connections) before it will work.

Main control board with the SW1 DIP switch highlighted; close-up showing pole 2 — slide left for ON (hot water off), slide right for OFF (hot water on)
SW1 location on the main control board, with a close-up of the switch. Pole 2 left = ON (hot water off) · right = OFF (hot water on).

Configure DHW temperatures (installer)

Open … › System Parameter › DHW MODE SET and set the start/target values and tank heater:

Menu › Installer Level › System Parameter
DHW MODE SET
01 Tb (start ΔT)5℃
02 Tx (target max)65℃
05 TANK HEATEREnable
06 P_d_DHWDisable

Tb = start delta below target · Tx = target tank temperature. Set TANK HEATER to Disable if no electric booster is fitted.

1-zone or 2-zone operation

The number of heating/cooling circuits is set in … › System Parameter › TEMP. TYPE SET with 01 ZONE TYPE. Set this first, then follow the matching block below.

If you use ONE zone

A single circuit fed by the main circulation pump (P_o). This is the typical setup.

Menu › Installer Level › System Parameter
TEMP. TYPE SET
01 ZONE TYPEONE
02 SINGLE ZONE OPERATION0

Set ZONE TYPE = ONE. 02 SINGLE ZONE OPERATION sets fixed vs weather-curve target — see Weather compensation.

Wire the Zone 1 / main circulation pump to CON1 ⑤ (P_o).

Set the Zone 1 emitter type — see Emitter type per zone below.

Set how Zone 1 follows the temperature (fixed or weather curve) with 02 SINGLE ZONE OPERATION — see Weather compensation.

If you use TWO zones

Zone 1 (usually the high-temp / direct circuit) plus Zone 2 (usually a mixed low-temp circuit, e.g. underfloor) fed through a mixing valve.

Menu › Installer Level › System Parameter
TEMP. TYPE SET
01 ZONE TYPETWO
03 DUAL ZONE OPERATION0

Set ZONE TYPE = TWO. 03 DUAL ZONE OPERATION sets each zone's target type — see Weather compensation.

Wire the Zone 2 pump to CON1 ④ (P_c / Pumpc) and the Zone 2 mixing valve SV3 to CON1 ③ (OFF3 / ON3 / N).

Fit a Zone 2 water-temperature sensor (TZ2) and, if used, the Zone 2 room thermostat.

Set the emitter type for each zone — see Emitter type per zone below.

Set each zone's target type with 03 DUAL ZONE OPERATION — see Weather compensation.

Configure the mixing valve — see below.

Set the Zone 2 mixing valve (SV3)

Open … › System Parameter › MIXING VALVE SET. These tune how the SV3 motorised valve opens/closes to hold the Zone 2 water temperature:

Menu › Installer Level › System Parameter
MIXING VALVE SET
01 TZ2Enable
02 t_SV3_ON5MIN
03 t_SV3_OFF2MIN
04 dT_SV3_ON5℃
05 dT_SV3_OFF0℃

01 TZ2 = enable the Zone 2 temperature sensor (must be Enable for mixed Zone 2). t_SV3_ON/OFF = valve drive time per step; dT_SV3_ON/OFF = temperature deviation that triggers the valve to open/close.

Leave the timing/deviation values at their defaults unless Zone 2 over- or under-shoots its target; then adjust in small steps.

Emitter type per zone — FCU / radiator / floor

Tell the controller what each zone feeds so it manages temperatures correctly. Set it separately for heating and (if used) cooling.

0 = FCU (fan coil)1 = Radiator2 = Floor heating

Heating

Open … › System Parameter › HEATING MODE SET:

Menu › Installer Level › System Parameter
HEATING MODE SET
01 ZONE1 HEAT-TYPE1 (Radiator)
02 ZONE2 HEAT-TYPE2 (Floor)
03 HIGH TEMP HEATDisable

Cooling (if the system cools)

Open … › System Parameter › COOLING MODE SET:

Menu › Installer Level › System Parameter
COOLING MODE SET
01 ZONE1 COOL-TYPE0 (FCU)
02 ZONE2 COOL-TYPE0 (FCU)

Floor cooling (value 2) is only allowed on a zone driven by the wired controller, not a room thermostat.

Activate / deactivate weather compensation

With weather compensation on, the controller sets the target water temperature from the outdoor air temperature using a climate curve, instead of a fixed setpoint — warmer outside means cooler water, which saves energy. Turning it on is two steps: enable it per zone (Step 1), then choose the curve (Step 2).

Step 1 — enable it per zone

In … › System Parameter › TEMP. TYPE SET, set the operation value. A "fixed" value means weather compensation is OFF; any "curve" value turns it ON.

One zone (ZONE TYPE = ONE)

Set 02 SINGLE ZONE OPERATION:

0 = fixed water temp — OFF1 = weather-curve water temp — ON3 = room temp + weather curve — ON

Two zones (ZONE TYPE = TWO)

Set 03 DUAL ZONE OPERATION — this picks the target type for Zone 1 and Zone 2 together:

ValueZone 1Zone 2Comp.
0fixed waterfixed waterOFF
1fixed waterweather curveZone 2
3fixed waterroom + weather curveZone 2
4weather curvefixed waterZone 1
5weather curveweather curveBoth
7weather curveroom + weather curveBoth

To deactivate weather compensation, set the operation value back to a fixed-water-temp option (single zone → 0; two zones → 0), and the unit follows the manual setpoint again.

Step 2 — choose the curve

Open … › System Parameter › WEATHER TEMPERATURE CURVE SET and set the curve number for each zone and mode:

Menu › Installer Level › System Parameter
WEATHER TEMP. CURVE SET
03 A-H LOW TEMP.CURVE3
04 A-H HIGH TEMP.CURVE6
07 B-H LOW TEMP.CURVE3
08 B-H HIGH TEMP.CURVE6

A = Zone 1, B = Zone 2 · H = heating, C = cooling. So 03 A-H = Zone 1 heating, 07 B-H = Zone 2 heating.

Reading the curve parameters

Each zone/mode has both a LOW and a HIGH curve slot; the controller automatically uses the one that matches the emitter type you set for that zone:

SlotUsed when emitter is…Produces
LOW temp curveFloor heating (low-temp)Lower water temperatures
HIGH temp curveRadiator or FCU (high-temp)Higher water temperatures

So for an underfloor zone, the LOW curve is what takes effect; for radiators or fan coils, the HIGH curve. There are 8 preset curves per slot (1–8): a higher number gives a hotter target at the same outdoor temperature.

Individual (custom) curve — the 9th curve

If none of the 8 presets fit the building, select curve number 9 — "Custom curve". This lets you define your own outdoor-temperature → water-temperature relationship for that zone and mode, rather than using a preset.

The custom curve points are entered on the controller's User Control › Weather Compensation page (also reachable to the end user). While any weather-compensation curve is active, the desired water temperature can't be set directly on the home page — it follows the curve.

04First power-up checklist

Work top to bottom. Don't apply power until every item under "before power-up" is confirmed.

Before power-up

The main switch must be OFF while you check the switch box. Verify each item below before switching on the circuit breaker.

Field wiring between supply panel, unit and valves matches the supplied wiring diagram, with the right wire size and a correctly rated breaker / RCD (30 mA, <0.1 s).

Earth is connected; earth-leakage protection is fitted.

Internal wiring — visually check for loose connections or damaged components.

Water circuit is filled, air purged, and pressure is 0.10–0.20 MPa (≈1–2 bar cold).

Shut-off valves are fully open.

Stop valves (gas/liquid) are open.

DIP switches (SW1–SW4) on the main board match the installation — set these with the power OFF.

Power up & configure

  1. Switch on the supply. The controller lights up; the indicator LED is steady-on when the unit is off.
  2. Enter Installer Level (passcode 1212) → System Parameter.
  3. Set ZONE TYPE, then the emitter type per zone, weather compensation, and confirm DHW — as in Section 03.

Initial run

For a fresh concrete/screed floor, raise water temperature gradually — rapid heating can crack the slab. Follow the screed contractor's drying schedule.

Verify correct operation in each mode the system uses (heating, DHW, cooling).

Close all panels and refit the cover before leaving the unit running.

During the first running period the input power can be higher than stated and consumption less stable while the compressor settles — this is normal.

05Common error codes

Codes show on the controller when a protection trips. Reset by turning the unit OFF and back ON; if the same code returns, diagnose before resetting again. The full list is in the service manual.

Protection codes (P)

CodeMeaningFirst checks
P01Water-flow protectionOpen closed valves, clean Y-filter, purge air, check flow switch.
P02High-pressure protectionLow water flow, HP switch fault, refrigerant blockage or EXV locked.
P03Low-pressure protectionRefrigerant shortage/leak, system blocked, running out of range.
P04Condenser over-tempPoor outdoor airflow, dirty condenser, T3 sensor fault.
P05Discharge-temp protectionRefrigerant shortage or discharge sensor fault.
P06Anti-freeze (leaving water)Low flow, blocked exchanger / filter, load too low.
P11/P12DC fan 1 / 2 failureFan stuck or main board fault.
P14Refrigerant leakageLeak in system, leak sensor fault, or PCB fault.
P21DC pump abnormalPump blocked, low water, or board fault.

Error codes (E)

CodeMeaningFirst checks
E01Controller communication errorCheck cable/plug between controller and unit (U19); replace controller, then board.
E02TP discharge sensor faultCheck sensor wiring; swap with a known-good sensor; replace board.
E03–E09Temp-sensor faults (T3, T4, T5, etc.)Same sequence as E02 — wiring, then sensor, then board.
E15–E36Drive / inverter module errorsInverter or compressor side — refer to the service manual.

Always switch off the main switch before inspecting the switch box. If a safety device tripped, find the cause first — safety devices must never be bridged or replaced with a different rating.